BBLU-D-FL DIMENSIONS & INDEX REFERENCE
FIGURE DIMENSIONS (IN.)
INSTALLATION TOOLING
COPPER CONDUCTOR SIZE
STUD HOLE SIZE
STUD HOLE SPACING
TONGUE WIDTH “W”
TONGUE LENGTH “C”
TONGUE THICKNESS “T”
BARREL LENGTH “B”
OVERALL LENGTH “L”
COLOR CODE
PENN-UNION DIELESS MECHANICAL TOOL
BURNDY DIE INDEX NO. /TOOL
T&B DIE INDEX NO.
WIRE STRIP LENGTH
CATALOG NO.
BBLU-3D-FL
3 AWG 5/16”
0.88
0.53 1.63 0.09 1.13 3.03 White
TDM-250XF
9
-
1-1/4”
BBLU-1D-FL
1 AWG 5/16”
0.88
0.67 1.63 0.11 1.38 3.38 Green
TDM-250XF
11
37
1-1/2”
BBLU-1/0D-FL BBLU-2/0D-FL BBLU-3/0D-FL
1/0 AWG 5/16” 2/0 AWG 1/2”
0.88 1.75 1.75
0.73 1.59 0.13 1.38 3.31 Pink 0.82 3.00 0.12 1.50 4.84 Black 0.89 3.00 0.13 1.50 4.91 Orange
TDM-250XF TDM-250XF TDM-250XF
12 13 14
42 45 50
1-1/2” 1-5/8” 1-5/8”
3/0 AWG 1/2”
BBLU-4/0D-FL
4/0 AWG 1/2”
1.75
1.00 3.00 0.14 1.63 5.10 Purple
TDM-250XF
15
54
1-3/4”
BBLU-030D-FL BBLU-035D-FL
300 kcmil 350 kcmil
1/2” 1/2”
1.75 1.75
1.19 3.00 0.16 2.00 5.59 White
17 18
66H/66 2-1/8” 71H/71 2-1/8”
1.28 3.00 0.17 2.00 5.66
Red
BBLU-040D-FL
400 kcmil
1/2”
1.75
1.39 3.00 0.19 2.13 5.79 Blue
19
76H/76 2-1/4”
BBLU-050D-FL
500 kcmil
1/2”
1.75
1.53 3.00 0.21 2.25 6.03 Brown
20
87
2-3/8”
BBLU-060D-FL
600 kcmil
1/2”
1.75
1.72 3.00 0.27 2.69 6.56 Green
22
94H/94 2-3/4”
BBLU-065D-FL
650 kcmil
1/2”
1.75
1.78 3.00 0.27 2.81 6.68 Pink
300
99 2-15/16”
BBLU-075D-FL
750 kcmil
1/2”
1.75
1.91 3.00 0.27 2.88 6.85 Black
24 106H/106 3”
BBLU-080D-FL
800 kcmil
1/2” 1/2” 5/8”
1.75 1.75 1.75
1.97 3.00 0.25 2.94 7.00 Orange
25 107H/107 3-1/16”
BBLU-100D1-FL BBLU-100D3-FL
2.17 3.00 0.33 3.00 7.16 2.17 3.00 0.33 3.00 7.16
1000 kcmil
White
27
125
3-1/8”
BBLU-150D1-FL
1500 kcmil
1/2”
1.75
2.69 3.00 0.39 3.19 7.44 Green
31
-
3-5/16”
For additional wire size recommendations please refer to page 55 • For 45° or 90° BENT TANGS add suffix “-45” for 45 deg. or “-90” for 90 deg. to the catalog number
• Connectors from 8 AWG - 2000 kcmil are UL Listed per UL486A-B and CSA Certified per C22.2 No.65 for POWER applications • Connectors from 8 AWG - 500 kcmil are UL Listed for grounding, bonding and direct burial applications per UL467 • Connectors from 8 AWG - 250 kcmil are CSA Certified for grounding, bonding and direct burial applications per C22.2 No.41
39
Powered by FlippingBook