Penn-Union Master Catalog

PENN-UNION PARALLEL RATED ALUMINUM PRE-INSULATED POWER BAR CONNECTORS TYPES: IPB, IPBM, IPBB, IPBBM

INSTALLATION INSTRUCTIONS FOR PARALLELING APPLICATIONS ONLY ALLOWABLE INSTALLATION CONFIGURATIONS INCLUDE:

2 CONDUCTORS IN PARALLEL WHEN USING A 4 POSITION CONNECTOR 3 CONDUCTORS IN PARALLEL WHEN USING A 6 POSITION CONNECTOR

AL9CU

4 CONDUCTORS IN PARALLEL WHEN USING A 8, 10, 12 OR 14 POSITION CONNECTOR 4 CONDUCTORS IN PARALLEL IS THE MAXIMUM APPROVED FOR USE IN THIS SERIES * MAX. CURRENT RATINGS ARE PER UL AND THE NEC THE SELECT CONNECTOR / CONDUCTOR CONFIGURATIONS BELOW ARE COMPLIANT WITH UL AND THE NEC WHEN INSTALLED AND OPERATED IN ACCORDANCE WITH THE APPLICATION CRITERIA BELOW

CLASS B AND C STRANDED COPPER AND ALUMINUM CONDUCTOR RANGE FOR PARALLELING APPLICATIONS

MAX. NUMBER OF CONDUCTORS IN PARALLEL

COPPER CONDUCTOR MAX. AMPS

CLEAR INSULATED IPB (S,D &A) SERIES

CLEAR INSULATED IPBM (S&D) SERIES

BLACK INSULATED IPBB (S,D &A) SERIES

BLACK INSULATED IPBBM (S&D) SERIES

ALUMINUM CONDUCTOR MAX. AMPS

IPB-NA2/0-4 IPB-NA2/0-6 IPB-NA2/0-8 IPB-NA2/0-10 IPB-NA2/0-12 IPB-NA2/0-14 IPB-NA250-4 IPB-NA250-6 IPB-NA250-8 IPB-NA250-10 IPB-NA250-12 IPB-NA250-14 IPB-NA350-4 IPB-NA350-6 IPB-NA350-8 IPB-NA350-10 IPB-NA350-12 IPB-NA350-14 IPB-NA600-4 IPB-NA600-6 IPB-NA600-8 IPB-NA600-10 IPB-NA600-12 IPB-NA600-14 IPB-NA750-4 IPB-NA750-6 IPB-NA750-8 IPB-NA750-10 IPB-NA750-12 IPB-NA750-14 IPB-NA1000-4 IPB-NA1000-6 IPB-NA1000-8

IPBM-NA2/0-4 IPBM-NA2/0-6 IPBM-NA2/0-8 IPBM-NA2/0-10 IPBM-NA2/0-12

IPBB-NA2/0-4 IPBB-NA2/0-6 IPBB-NA2/0-8 IPBB-NA2/0-10 IPBB-NA2/0-12 IPBB-NA2/0-14 IPBB-NA250-4 IPBB-NA250-6 IPBB-NA250-8 IPBB-NA250-10 IPBB-NA250-12 IPBB-NA250-14 IPBB-NA350-4 IPBB-NA350-6 IPBB-NA350-8 IPBB-NA350-10 IPBB-NA350-12 IPBB-NA350-14 IPBB-NA600-4 IPBB-NA600-6 IPBB-NA600-8 IPBB-NA600-10 IPBB-NA600-12 IPBB-NA600-14 IPBB-NA750-4 IPBB-NA750-6 IPBB-NA750-8 IPBB-NA750-10 IPBB-NA750-12 IPBB-NA750-14 IPBB-NA1000-4 IPBB-NA1000-6 IPBB-NA1000-8

IPBBM-NA2/0-4 IPBBM-NA2/0-6 IPBBM-NA2/0-8 IPBBM-NA2/0-10 IPBBM-NA2/0-12

2 3 4 4 4 4 2 3 4 4 4 4 2 3 4 4 4 4 2 3 4 4 4 4 2 3 4 4 4 4 2 3 4 4 4 4

350 525 560 560 560 560 527 790

270 405 432 432 432 432 410 615 820 820 820 820 514 770

2/0 - 1/0 AWG

-

-

IPBM-NA250-4 IPBM-NA250-6 IPBM-NA250-8 IPBM-NA250-10 IPBM-NA250-12

IPBBM-NA250-4 IPBBM-NA250-6 IPBBM-NA250-8 IPBBM-NA250-10 IPBBM-NA250-12

1053 1053 1053 1053

250 MCM - 1/0 AWG

-

-

IPBM-NA350-4 IPBM-NA350-6 IPBM-NA350-8 IPBM-NA350-10 IPBM-NA350-12

IPBBM-NA350-4 IPBBM-NA350-6 IPBBM-NA350-8 IPBBM-NA350-10 IPBBM-NA350-12

657 985

1314 1314 1314 1314 1035 1554 2070 2070 2070 2070 1178 1767 2356 2356 2356 2356 1403 2104 2806 2806 2806 2806

1028 1028 1028 1028

350 MCM - 1/0 AWG

-

-

IPBM-NA600-4 IPBM-NA600-6 IPBM-NA600-8 IPBM-NA600-10 IPBM-NA600-12

IPBBM-NA600-4 IPBBM-NA600-6 IPBBM-NA600-8 IPBBM-NA600-10 IPBBM-NA600-12

810

1215 1620 1620 1620 1620

600 MCM - 1/0 AWG

-

-

IPBM-NA750-4 IPBM-NA750-6 IPBM-NA750-8 IPBM-NA750-10 IPBM-NA750-12

IPBBM-NA750-4 IPBBM-NA750-6 IPBBM-NA750-8 IPBBM-NA750-10 IPBBM-NA750-12

930

1395 1860 1860 1860 1860 1125 1688 2250 2250 2250 2250

750 MCM - 1/0 AWG

-

-

IPBM-NA1000-4 IPBM-NA1000-6 IPBM-NA1000-8

IPBBM-NA1000-4 IPBBM-NA1000-6 IPBBM-NA1000-8 IPBBM-NA1000-10 IPBBM-NA1000-12

1000 MCM - 1/0 AWG

IPB-NA1000-10 IPBM-NA1000-10 IPBB-NA1000-10 IPB-NA1000-12 IPBM-NA1000-12 IPBB-NA1000-12

IPB-NA1000-14

-

IPBB-NA1000-14

-

Notes: Per UL486A/B Table 8 1) The current values for conductor sizes 1/0 - 4/0 AWG are based on the National Electrical Code (NEC), ANSI/NFPA 70, Table 310.16, 75°C column, multiplied by the number of conductors. The current for the 4 parallel conductors is additionally adjusted to 80% based on Table 310-15(C)(1). 2) The current values for conductor sizes 250 MCM and larger are in accordance with the NEC, NFPA 70, Sections 392.80(A)(2)(a) and 392.80 (A)(2)(b) for table 310.17, 75°C column, multiplied by the number of conductors and adjusted as follows: 250 - 500 MCM - adjusted to 65 percent 600 MCM and larger - adjusted to 75 percent NOTE: CONDUCTOR RANGES MARKED ON THE CONNECTORS ARE FOR NON-PARALLELING APPLICATIONS. ONLY THE CONDUCTOR RANGES NOTED ABOVE ARE APPROVED FOR PARALLELING APPLICATIONS.