Penn-Union Master Catalog

BBLU-D-FL DIMENSIONS & INSTALLATION TOOLING INFORMATION

FIGURE DIMENSIONS (IN.)

INSTALLATION TOOLING

COPPER CONDUCTOR SIZE

STUD HOLE SIZE

WIRE STRIP LENGTH

PENN-UNION DIE CATALOG NO.

TONGUE LENGTH “C”

BARREL LENGTH “B”

OVERALL LENGTH “L”

TONGUE WIDTH “W”

TONGUE THICKNESS “T”

BURNDY DIE INDEX NO.

CATALOG NUMBER

STUD HOLE SPACING

PENN-UNION DIELESS MECHANICAL TOOL

COLOR CODE

BBLU-3D-FL

3 AWG 5/16

.88

.53 1.63 .09 1.13 3.03 White

9

T-9

1-1/4”

BBLU-1D-FL

1 AWG 5/16

.88

.67 1.63 .11 1.38 3.38 Green

11

T-11 1-1/2”

BBLU-1/0D-FL BBLU-2/0D-FL BBLU-3/0D-FL

1/0 AWG 5/16 2/0 AWG 1/2

.88

.73 1.59 .13 1.38 3.31 Pink .82 3.00 .12 1.50 4.84 Black .89 3.00 .13 1.50 4.91 Orange

12 13 14

T-12 1-1/2” T-13 1-5/8” T-14 1-5/8”

TDM-250XF

1.75 1.75

3/0 AWG 1/2

BBLU-4/0D-FL

4/0 AWG 1/2

1.75

1.00 3.00 .14 1.63 5.10 Purple

15

T-15 1-3/4”

BBLU-030D-FL BBLU-035D-FL

300 kcmil 350 kcmil

1/2 1/2

1.75 1.75

1.19 3.00 .16 2.00 5.59 White

17 18

T-17 2-1/8” T-18 2-1/8”

1.28 3.00 .17 2.00 5.66

Red

BBLU-040D-FL

400 kcmil

1/2

1.75

1.39 3.00 .19 2.13 5.79 Blue

19

T-19 2-1/4”

BBLU-050D-FL

500 kcmil

1/2

1.75

1.53 3.00 .21 2.25 6.03 Brown

20

T-20 2-3/8”

BBLU-060D-FL

600 kcmil

1/2

1.75

1.72 3.00 .27 2.69 6.56 Green

22

T-22 2-3/4”

BBLU-065D-FL

650 kcmil

1/2

1.75

1.78 3.00 .27 2.81 6.68 Pink

300

T-300 2-15/16”

BBLU-075D-FL

750 kcmil

1/2

1.75

1.91 3.00 .27 2.88 6.85 Black

24

T-24

3”

BBLU-080D-FL

800 kcmil

1/2 1/2 5/8

1.75 1.75 1.75

1.97 3.00 .25 2.94 7.00 Orange

25

T-25P 3-1/16”

BBLU-100D1-FL BBLU-100D3-FL

2.17 3.00 .33 3.00 7.16 2.17 3.00 .33 3.00 7.16

1000 kcmil

White

27

T-27P 3-1/8”

BBLU-150D1-FL

1500 kcmil

1/2

1.75

2.69 3.00 .39 3.19 7.44 Green

31

T-31P 3-5/16”

For additional wire size recommendations please refer to page 81 • For 45° or 90° BENT TONGUES add suffix “-45” for 45 deg. or “-90” for 90 deg. to the catalog number

• Connectors from 8 AWG - 2000 kcmil are UL listed per UL486A-B and CSA certified per C22.2 No.65 for POWER applications • Connectors from 8 AWG - 500 kcmil are UL listed for grounding, bonding and direct burial applications per UL467 • Connectors from 8 AWG - 250 kcmil are CSA certified for grounding, bonding and direct burial applications per C22.2 No.41

41

Powered by